Go to main content

Data subject to change without notice. Always confirm the data is correct from the seller.

KEA 3160 A4EX 2XM40PEX KST16MEX

ATEX Switches 16-160A

  • Conforming to Directive 2014/34/EU, EN 60079-0 (2012), EN 60079-31 (2014)
  • Suitable for use in Zone 22 (Category 3D)
  • IP66
  • Frontal impact test of 7 Joules
  • Temperature range from -20 °C to +40°C
  • Available in aluminium and stainless steel
  • Padlockable with three locks
  • Door interlock with defeat mechanism
  • Separate ATEX-enclosures upon request
  • ATEX cable glands included
  • Tested according to IEC 60947-3
  • Available as EX EMC
  • Note! Al-cables cannot be connected directly to switch terminals. For Al-cable connection please use a bi-metal cable connector, available here.

Technical datasheet >>

Accessories

Product details

SKU KEA 3160 A4EX 2XM40PEX KST16MEX
AC-21 400/415 V (A) 160 A
AC-21 690 V (A) 160 A
AC-22 400/415 V (A) 160 A
AC-22 690 V (A) 160 A
AC-23 400/415 V (A/kW) 160 A / 90 kW
AC-23 690 V (A/kW) 100 A / 90 kW
Cable Area to Switch Terminal (only Cu) (mm2) / Bolt size 6-70
Cable Gland 2xM40
Color Standard
EAN 6419410305591
Enclosure A4
Enclosure Type Aluminium
IP Rating 66
Number of Poles 3
Operation Front-operated
Switch type Load Break Switch
Weight (kg) 3.8

Dimensional drawing

Product diagram