E-number FI
GTIN
6419410372807
Rated operational current AC-23A 415V (A)
80
Enclosure type
Aluminium enclosure
Enclosure
A4EX
Product details and documents
Technical data
Cable entries
2 x M40 (19,0-28,0 mm), metal EX; 1 x M16 (5,0-10,0 mm), metal EX
Depth
108 mm
EMC
false
Enclosure
A4EX
Enclosure type
Aluminium enclosure
ETIM Class
EC000522
EX
true
E-number FI
3600899
GTIN
6419410372807
Height
262 mm
Max. term. torque (Nm)
6
Mech. endurance (no. of oper.)
16000
Net weight
3.055 kg
Nom. values w/cable size (mm²)
70
Number of poles
3
Product type
KUA 380 1V A4EX 2XM40MEX M16MEX
Rated breaking cap. ICN AC-23A 415V (A)
640
Rated breaking cap. ICN AC-23A 500V (A)
640
Rated breaking cap. ICN AC-23A 690V (A)
640
Rated fused short-ckt current back-up fuse opt 1 (A)
160
Rated fused short-ckt current peak value (kA)
15
Rated fused short-ckt current RMS Ik opt 1 (kA)
65
Rated fused short-ckt. impulse withstand volt. Uimp (kV)
8
Rated insulation volt. Ui (V)
800
Rated operational current AC-21A 415V (A)
125
Rated operational current AC-21A 500V (A)
125
Rated operational current AC-21A 690V (A)
125
Rated operational current AC-22A 415V (A)
100
Rated operational current AC-22A 500V (A)
100
Rated operational current AC-22A 690V (A)
100
Rated operational current AC-23A 415V (A)
80
Rated operational current AC-23A 500V (A)
63
Rated operational current AC-23A 690V (A)
63
Rated oper. power 3-ph 1500rpm SQ cage motor AC-23A 415V (kW)
45
Rated oper. power 3-ph 1500rpm SQ cage motor AC-23A 500V (kW)
37
Rated oper. power 3-ph 1500rpm SQ cage motor AC-23A 690V (kW)
55
Rated short-ckt. making cap. Icm 690V (kA)
8
Rated short-time withstand current 1s Icw 690V (kA)
5
Rated therm. current Ithe (A)
125
Rated therm. current Ith (A)
125
Switch type
Load Break Switch
Technical name
3x80A 400V ATEX II 3D
Terminals bolt size (Cu mm²)
6..70
Volume
4.584 l
Width
162 mm
Dimensional drawing
Logistical data
Not finding what you're looking for? We're here to help!
We can assist you with technical support, quote or tailoring options for this product
Latest News & Insights
-
Discontinuation of 3-pole EVA and VKA 80–160A Switches
23.6.2025 -
Introducing the Refreshed LK10 handle: New Fresh Design, Same Trusted Performance
2.9.2024 -
KATKO Has Published Its First 'Sustainability at KATKO' Report
8.11.2024 -
KATKO KL Terminal Blocks Comply with the Requirements of the IEC TS 60947-7-5 Technical Specification
29.4.2025 -
KATKO LoadSafe Product Family – New Additions, Now Available
14.1.2025 -
Katko Products Available on EPLAN Data Portal
14.9.2023 -
KATKO Strengthens Presence in Sweden: Kim Rannanjärvi Appointed Sales Manager
28.7.2025 -
KATKO Strengthens Presence in UK: Ian Bullock Appointed Sales Director
10.11.2025 -
New Front Plate for KU 16–40A Switch Series
26.8.2025 -
Jyrki Luomi has been appointed as the Commercial Director of Katko Oy
17.9.2024 -
Product Update: Extended Cable Range for 95-Series Connectors
30.10.2025 -
The Core of Responsible and Transparent Collaboration – Partner Code of Conduct
6.2.2025
1
/
z
3