Manual motor controller 4x40A

- KEA 440UL A2

Manual motor controller 4x40A

Katko UL/cUL listed aluminium enclosed disconnect switches are designed for demanding industrial and commercial applications where safety, compliance and reliable disconnection are essential. Featuring a Type 4 aluminium enclosure, they provide strong mechanical protection, good corrosion resistance and efficient heat dissipation, ensuring dependable operation in both indoor and outdoor environments.

The switches support across-the-line motor starting up to 75 HP at 600 V and are suitable for a wide range of motor and load disconnect applications. Certified according to UL and CSA requirements and compliant with UL 60947-4-1A, they meet the expectations of North American installations where performance and regulatory compliance are critical. Developed using Katko’s application-driven engineering approach, these disconnect switches deliver long-term reliability and safe electrical distribution wherever durability and proven standards matter.

GTIN
6419410348475
Ampere rating 600V
40
Enclosure type
Aluminium
Enclosure
A2 (104 x 159 x 80 mm)
View full details

Product details and documents

Technical data

Ampere rating 600V
40.0
Depth
79.5 mm
EMC
false
Enclosure
A2 (104 x 159 x 80 mm)
Enclosure type
Aluminium
ETIM Class
EC000216
GTIN
6419410348475
Height
158.5 mm
HP 208V
7.5
HP 415V
10.0
HP 480V
20.0
HP 600V
15.0
IP rating
IP66
Long product name
UL-listed, 4-pole, Aluminum enclosure; W104 x H158.5 x D79.5
Max. term. torque (Nm)
1.8
Mech. endurance (no. of oper.)
50000
Net weight
1.0926 kg
Nom. values w/cable size (mm²)
16
Number of poles
4
Product type
- KEA 440UL A2
Rated breaking cap. ICN AC-23A 415V (A)
320
Rated breaking cap. ICN AC-23A 500V (A)
256
Rated breaking cap. ICN AC-23A 690V (A)
256
Rated fused short-ckt current back-up fuse opt 1 (A)
40
Rated fused short-ckt current peak value (kA)
6
Rated fused short-ckt current RMS Ik opt 1 (kA)
50
Rated fused short-ckt. impulse withstand volt. Uimp (kV)
8
Rated insulation volt. Ui (V)
800
Rated operational current AC-21A 415V (A)
63
Rated operational current AC-21A 500V (A)
63
Rated operational current AC-21A 690V (A)
63
Rated operational current AC-22A 415V (A)
40
Rated operational current AC-22A 500V (A)
40
Rated operational current AC-22A 690V (A)
40
Rated operational current AC-23A 415V (A)
40
Rated operational current AC-23A 500V (A)
32
Rated operational current AC-23A 690V (A)
32
Rated oper. power 3-ph 1500rpm SQ cage motor AC-23A 415V (kW)
22
Rated oper. power 3-ph 1500rpm SQ cage motor AC-23A 500V (kW)
22
Rated oper. power 3-ph 1500rpm SQ cage motor AC-23A 690V (kW)
30
Rated short-ckt. making cap. Icm 690V (kA)
2.5
Rated short-time withstand current 1s Icw 690V (kA)
1.7
Rated therm. current Ithe (A)
63
Rated therm. current Ith (A)
63
Short product description
Manual motor controller 4x40A
Switch type
Load Break Switch
Technical name
4x40A 400V 22kW
Terminals bolt size (Cu mm²)
1,5..16
UL
UL 60947-4-1A
Volume
1.3105 l
Width
104 mm
Wire size Cu
14-8AWG

Dimensional drawing

Logistical data

Package size 1 depth
120 mm
Package size 1 GTIN code
6419410295847
Package size 1 height
200 mm
Package size 1 volume
3.6 l
Package size 1 width
150 mm

Not finding what you're looking for? We're here to help!